Battery backup calculator.

Estimate nominal battery kWh and amp-hours from backup load, duration, voltage and usable capacity.

Battery backup inputs

W
hours
V
%
%
YOUR RESULTS
Minimum nominal battery2.778 kWh
Capacity at selected voltage115.741 Ah
Energy required by loads2 kWh

Allow separately for inverter surge, battery aging, temperature and manufacturer limits. Trust level: engineering estimate; verify site and equipment assumptions before purchase or installation.

View detailed breakdown
AssumptionValue
Battery-bank voltage24 V
Usable depth of discharge80 %
Inverter and wiring efficiency90 %
HOW THIS RESULT WAS BUILTEngineering estimateEngine energy-1.0.0

Method: battery Wh = load W × hours ÷ (depth of discharge × efficiency)

Inputs used: 500 × 4 ÷ (80% × 90%) = 2777.7777777777774 Wh

Assumptions: Battery-bank voltage Usable depth of discharge Inverter and wiring efficiency

Scope and warnings: Allow separately for inverter surge, battery aging, temperature and manufacturer limits.

Sources and coefficient scope
Solar energy and storage basics

U.S. Department of Energy · United States government educational resource; technology concepts are broadly applicable · effective As published · reviewed 2026-09-12

high confidence · Engineering estimate

Supports the distinction between power, energy and storage-system limitations.

Exclusions: Not a product-sizing recommendation or outage-resilience guarantee.

UNDERSTAND THE RESULT

How this battery backup calculator works

Required load energy is watts multiplied by hours. Nominal battery energy is larger because only the chosen depth of discharge is usable and conversion loses energy. Amp-hours then divide nominal watt-hours by battery-bank voltage.

A worked example

A 500 W backup load for 4 hours needs 2 kWh at the loads. At 80% depth of discharge and 90% efficiency, minimum nominal storage is about 2.78 kWh, or 115.7 Ah at 24 V.

Does this size the inverter too?

No. Battery energy and inverter power are different constraints. Size inverter continuous and surge power for the connected loads, then account for battery age, temperature, wiring and manufacturer limits.

References and further reading

Calculations run on your device. Review your results before exporting or sharing them.

Start with the loads that must stay on

List essential loads and estimate their simultaneous watts before choosing hours of autonomy. The depth-of-discharge and efficiency inputs must match the battery chemistry, inverter and manufacturer guidance you expect to use.

The result is minimum nominal energy under the entered assumptions. Add design margin for surge, battery aging, temperature and future loads; compare inverter power independently with electrical load rather than equating kWh with kW.